A contactors LRA rating may be

A contactors LRA rating may be

Go to your truck, pick up a contactor, and look at it closely. You may find some interesting ratings you never noticed—things like terminal ambient temperature ratings and torque specs. One reading you may overlook is the RES AMPACITY of the contactor or relay. The RES rating is the RESISTIVE LOAD AMPACITY (amperage capacity) or rating.

Remember, a contactor or relay is both a switch (contacts) and a load (coil) that controls the switch (contacts). The FLA, RES, and LRA refer to the ratings of the switch/contacts/points portion of the relay or contactor, not the coil portion. The coil is just rated for voltage and cycle rate (Hz).

A contactors LRA rating may be

You will notice that the RES (resistive load) rating is higher than the FLA (full load amperage) rating. It's also much lower than the LRA (locked rotor amperage) rating. So, the contactor above would be sufficient to control/switch a 40 amp full load INDUCTIVE load and a 50-amp RESISTIVE load.

So, what is the difference between an inductive and a resistive load?

An inductive load is a magnetic load that converts electrical energy into kinetic energy (motion) through electromagnetic force (magnetism). That would usually refer to motors and solenoids in HVAC/R. It really refers to anything where magnetism and motion are involved. (Of course, for the purists in my audience, I can't neglect to mention that transformers and inductive ranges are examples of induction WITHOUT motion.)

A contactors LRA rating may be

An inductive load will experience a spike in current when voltage (potential) is first applied; this is called locked rotor amps (LRA) because it is the current a motor will draw when it starts up from a locked or stalled position.

A resistive load is a load that converts electrical energy directly to light or heat as the electrons flow through a resistive conductive path. These would be things like heat strips, crankcase heaters, and incandescent light bulbs. Resistive loads do not have any internal variation in load, and the voltage and amperage are completely in phase. That means that when a contactor, switch, or relay controls a resistive load, there will be less load variation.

The conclusion is that contactors and relays can often handle a higher amperage across the contacts when the load is resistive (light/heat) than when it is inductive (motor/motion).

—Bryan

A contactors LRA rating may be
Learning from the Past vs. Allowing it to Control You

In our line of work, it's all too easy to let your bad experiences inform your present and future experiences. That is especially true if you have a high emotional range. Having “emotional range” is a polite way of saying that you're a bit up and down (maybe even neurotic). We don’t believe that sensitivity […]

Read more

A contactors LRA rating may be
Which Valve Do I Open First?

Testo 557 vacuum gauge and Appion core removal tools shown I've had a change of heart. Back in the early 2000s, during the big construction boom, I did many system startups on residential units for a large company I worked for. When installers ran the line sets prior to startup, they weren't always very careful […]

Read more

A contactors LRA rating may be
Don't Use Barometric Pressure For Calibration

Take a look at the screenshots above. The one on the left is for Death Valley at 282′ below sea level, and the one on the right is Denver, CO, at 5,280′ above sea level. Notice the barometric pressure values; they are almost the same. That means that barometric pressure is corrected or “normalized” to […]

Read more

How is a contactor rated?

Ratings. Contactors are rated by designed load current per contact (pole), maximum fault withstand current, duty cycle, design life expectancy, voltage, and coil voltage.

What is Fla on a contactor?

FLA (Full load Amperes): This is motor (compressor) current when it is running at full load. This is generally inductive load with power factor @ 0.8. LRA (Locked Rotor Amperes): This is a locked rotor (starting) current of the motor (compressor).

What do the numbers on a contactor mean?

These auxiliary contacts (also called control contacts) each have an order number and a function number. The first number is used consecutively (order number) and the second number specifies the type of contact (function number).

Who sets the standards for motor overload protection?

The NEC states this overload device shall be sized at no more than 125% of the motor's FLA for motors with a service factor of 1.15 or more. Use an overload protection device with a rating of 30 amps because the rating cannot exceed 125% of the FLA. This overload protection device can be a fuse or circuit breaker.